What is a Circuit Breaker?
Schneider Electric |
Defines circuit breakers
as “devices designed to open and close a circuit by non-automatic means, and to
open the circuit automatically on a predetermined overcurrent without injury to
itself when properly applied within its rating.
a mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal circuit conditions such as those of short-circuit.
The Molded Case Circuit
Breaker is a specific type of circuit breaker. NEMA defines circuit breakers as
devices designed to open or close a circuit by nonautomatic means, and to open
the circuit automatically on a predetermined overcurrent without damage to
itself when properly applied within its rating. The term “molded case” simply
refers to the construction of the circuit breaker and refers to the fact that
the circuit breaker is an assembled unit in a supporting housing of an
insulating material.
What is the trip unit?
The traditional
molded-case circuit breaker uses electromechanical (thermal magnetic) trip
units that may be fixed or interchangeable. An MCCB provides protection by
combining a temperature sensitive device with a current sensitive
electromagnetic device. Both these devices act mechanically on the trip
mechanism.
Depending upon the application
and required protection, an MCCB will use one or a combination of different
trip elements that protect against the following conditions:
Thermal overloads; Short
circuits; and Ground faults.
1- Thermal overload.
In an overload condition, there's a temperature
buildup between the insulation and conductor. If left unchecked, the
insulation's life will drastically reduce, ultimately resulting in a short
circuit. This heat is a function of the square of the rms current (F), the
resistance in the conductor (R), and the amount of time the current flows (t).
If you monitor current
flow and time, you can somewhat predict and detect overload conditions. By
using a time-current curve, you can see the boundary between the normal and
overload conditions. Here, we see that the thermal or overload element of the
MCCB will initiate a trip in 1800 sec at 135% of rating, or in 10 sec at 500%
of rating
Short-circuit condition.
Usually, a short circuit
occurs when abnormally high currents flow as a result of the failure of an
insulation system. This high current flow, termed short-circuit current, is
limited only by the capabilities of the distribution system. To stop this
current flow quickly so that major damage can be prevented, the short circuit
or instantaneous element of an MCCB is used.
Ground fault condition.
A ground fault actually is
a type of short circuit, only it's phase-to-ground, which probably is the most
common type of fault on low-voltage systems (600V or less).
Usually, arcing
ground-fault currents are not large enough to be detected by the standard MCCB
protective device. But, if left undetected, they can increase sufficiently to
trip the standard protective device. When this happens, it usually is too late,
and the damage is already done. An example of this is a motor having an
internal insulation failure. While the current flow may be small, it must be
detected and eliminated before major motor damage takes place.
Prior to the introduction
of electronic CBs, separate ground fault protection devices were used to
provide this additional level of protection. Today's modern electronic CB has
the ground fault protection as an integral part of the trip unit.
Overload trip action
Overload or thermal trip
action uses a piece of bimetal heated by the load current. This bimetal is
actually two strips of metal bonded together, with each having a different
thermal rate of heat expansion. They are factory-calibrated and not
field-adjustable.
heat will cause the
bimetal to bend. That part of the bimetal having the greater rate of expansion
(shown in red) is on the outside of the bend curve. To trip the CB, this
bimetal must deflect enough to physically push the trip bar and unlatch the
contacts.
Short-circuit trip action
Short-circuit trip action
uses an electromagnet having a winding that's in series with the load current.
When a short circuit occurs, the current flowing through the circuit conductor
causes the magnetic field strength of the electromagnet to increase rapidly and
attract the armature,. When this happens, the armature rotates the trip bar,
causing the CB to trip.
The only time delay factor
involves the time it takes for the contacts to physically open and extinguish
the arc; this usually is less than one cycle.
Magnetic elements are
either fixed or adjustable, depending upon the type of CB and frame size. For
example, most thermal magnetic breakers above the 150A frame size have
adjustable magnetic trips.
Thermal magnetic trip
action
As the name implies, a
thermal magnetic trip unit combines the features of a thermal unit and a
magnetic unit,. As a result, the time current curve combines the performance
characteristics. For a typical 100A MCCB, A 250% overload will take
approximately 60 sec before the bi-metal will bend far enough to trip the CB .If
there is a short circuit, 400% of the CB's rating, instead of an overload,
however, the electromagnet will attract the armature and trip the breaker in
less than one cycle.
A thermal magnetic trip
unit is best suited to most general-purpose applications as it's temperature
sensitive and automatically will follow safe cable and equipment loadings.
These loadings will vary with ambient temperatures. Thermal magnetic units
don't trip if the overload isn't dangerous, but will trip instantly with heavy
short-circuit currents.
Electronic trip units
Electronic trip units
typically consist of a current transformer (CT) for each phase, a printed
circuit board, and a shunt trip. The CTs monitor current and reduce it to the
required ratio for direct input into the printed circuit board, the brains of
the electronic trip unit. The circuit board then interprets current flow
information, makes trip decisions based on predetermined parameters, and tells
the shunt trip unit to trip the breaker.
Great helpful! this blog is really help full of knowledge thank you for this information.
ReplyDeleteJS ElectroMec Ltd is the leading Industrial Automation Company in Tanzania that offers a full range of industrial automation and control if you are interested then contact us.
Industrial Control Systems Tanzania
more info;
https:// shop.jselectromec.com