Saturday, August 15, 2015

MCCB & Trip Unit

What is a Circuit Breaker?

Schneider Electric 
The definition of a circuit breaker varies between the standards organizations, but the most commonly used definitions are:  

Defines circuit breakers as “devices designed to open and close a circuit by non-automatic means, and to open the circuit automatically on a predetermined overcurrent without injury to itself when properly applied within its rating.

a mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal circuit conditions such as those of short-circuit.





The Molded Case Circuit Breaker is a specific type of circuit breaker. NEMA defines circuit breakers as devices designed to open or close a circuit by nonautomatic means, and to open the circuit automatically on a predetermined overcurrent without damage to itself when properly applied within its rating. The term “molded case” simply refers to the construction of the circuit breaker and refers to the fact that the circuit breaker is an assembled unit in a supporting housing of an insulating material.

What is the trip unit?


The traditional molded-case circuit breaker uses electromechanical (thermal magnetic) trip units that may be fixed or interchangeable. An MCCB provides protection by combining a temperature sensitive device with a current sensitive electromagnetic device. Both these devices act mechanically on the trip mechanism.
Depending upon the application and required protection, an MCCB will use one or a combination of different trip elements that protect against the following conditions:

Thermal overloads; Short circuits; and Ground faults.

1- Thermal overload.

 In an overload condition, there's a temperature buildup between the insulation and conductor. If left unchecked, the insulation's life will drastically reduce, ultimately resulting in a short circuit. This heat is a function of the square of the rms current (F), the resistance in the conductor (R), and the amount of time the current flows (t).
If you monitor current flow and time, you can somewhat predict and detect overload conditions. By using a time-current curve, you can see the boundary between the normal and overload conditions. Here, we see that the thermal or overload element of the MCCB will initiate a trip in 1800 sec at 135% of rating, or in 10 sec at 500% of rating

Short-circuit condition.

Usually, a short circuit occurs when abnormally high currents flow as a result of the failure of an insulation system. This high current flow, termed short-circuit current, is limited only by the capabilities of the distribution system. To stop this current flow quickly so that major damage can be prevented, the short circuit or instantaneous element of an MCCB is used.

Ground fault condition.

A ground fault actually is a type of short circuit, only it's phase-to-ground, which probably is the most common type of fault on low-voltage systems (600V or less).
Usually, arcing ground-fault currents are not large enough to be detected by the standard MCCB protective device. But, if left undetected, they can increase sufficiently to trip the standard protective device. When this happens, it usually is too late, and the damage is already done. An example of this is a motor having an internal insulation failure. While the current flow may be small, it must be detected and eliminated before major motor damage takes place.
Prior to the introduction of electronic CBs, separate ground fault protection devices were used to provide this additional level of protection. Today's modern electronic CB has the ground fault protection as an integral part of the trip unit.

Overload trip action

Overload or thermal trip action uses a piece of bimetal heated by the load current. This bimetal is actually two strips of metal bonded together, with each having a different thermal rate of heat expansion. They are factory-calibrated and not field-adjustable.
heat will cause the bimetal to bend. That part of the bimetal having the greater rate of expansion (shown in red) is on the outside of the bend curve. To trip the CB, this bimetal must deflect enough to physically push the trip bar and unlatch the contacts.

Short-circuit trip action

Short-circuit trip action uses an electromagnet having a winding that's in series with the load current. When a short circuit occurs, the current flowing through the circuit conductor causes the magnetic field strength of the electromagnet to increase rapidly and attract the armature,. When this happens, the armature rotates the trip bar, causing the CB to trip.
The only time delay factor involves the time it takes for the contacts to physically open and extinguish the arc; this usually is less than one cycle.
Magnetic elements are either fixed or adjustable, depending upon the type of CB and frame size. For example, most thermal magnetic breakers above the 150A frame size have adjustable magnetic trips.

Thermal magnetic trip action

As the name implies, a thermal magnetic trip unit combines the features of a thermal unit and a magnetic unit,. As a result, the time current curve combines the performance characteristics. For a typical 100A MCCB, A 250% overload will take approximately 60 sec before the bi-metal will bend far enough to trip the CB .If there is a short circuit, 400% of the CB's rating, instead of an overload, however, the electromagnet will attract the armature and trip the breaker in less than one cycle.
A thermal magnetic trip unit is best suited to most general-purpose applications as it's temperature sensitive and automatically will follow safe cable and equipment loadings. These loadings will vary with ambient temperatures. Thermal magnetic units don't trip if the overload isn't dangerous, but will trip instantly with heavy short-circuit currents.

Electronic trip units

Electronic trip units typically consist of a current transformer (CT) for each phase, a printed circuit board, and a shunt trip. The CTs monitor current and reduce it to the required ratio for direct input into the printed circuit board, the brains of the electronic trip unit. The circuit board then interprets current flow information, makes trip decisions based on predetermined parameters, and tells the shunt trip unit to trip the breaker.


1 comment:

  1. Great helpful! this blog is really help full of knowledge thank you for this information.

    JS ElectroMec Ltd is the leading Industrial Automation Company in Tanzania that offers a full range of industrial automation and control if you are interested then contact us.

    Industrial Control Systems Tanzania


    more info;
    https:// shop.jselectromec.com

    ReplyDelete