What is The MCB ?
There are some parameters should be taken in consider when choose suitable MCB in a circuit ;
Schneider Electric |
The definition of MCB is Miniature Circuit Breaker . MCB is electromechanical device which is used to protect electrical circuit from the overcurent which may caused due to ( short circuit , overloads or faulty design). It interrupts the continuity of electrical flow through the circuit once a fault is detected . now we can define the MCB as a switch which automatically turns off when the current flowing through it passes the maximum allowable limit.
There are some parameters should be taken in consider when choose suitable MCB in a circuit ;
1) Ampere rating ( In )
In = 1.25 X I load
for example if the load current is 25 A , the In = 1.25 x 25 = 31.25 so we can use breaker 32 A
2) Short circuit breaking capacity (KA)
One of the most important safety aspects to consider when designing an electrical circuit is to correctly size the circuit breaker fault current rating (commonly called the kA rating). Unfortunately many electricians are unaware of this concept, and it remains one of the most common design faults found in electrical circuits. In the last 10 years it has become very common in domestic wiring, because of changes in the way power is distributed to new houses.
The value of the kA rating determines how much current the circuit breaker can withstand under fault conditions. The circuit breaker only has to withstand this for a brief period of time, usually the time it takes for the circuit breaker to trip. For example, a value of 6kA means that the circuit breaker can withstand 6,000 amps of current during the brief time it takes to trip.
Under fault conditions (such as a short circuit) much more current flows through the circuit than what it was designed for. A circuit that was designed for a maximum of 20A may suddenly be drawing hundreds, if not thousands of amps. The circuit breaker will trip if this occurs.
However, what if during a short circuit there is more current flowing through the circuit than the kA rating of the circuit breaker? In this case the circuit breaker will fail, often in either one of two ways. One possibility is that the contacts in the circuit breaker will weld, thus preventing the circuit breaker from tripping. The best case scenario for this is that the cable in the circuit is damaged. The worst case is that a fire is started. Another possibility is that the circuit breaker explodes, as a result of the copper in the circuit breaker overheating and turning into dangerous plasma. This could be very dangerous to people nearby, for example the electrician turning the circuit breaker on after a fault.
The maximum amount of current that can flow through a circuit is determined by the size of the transformer feeding the circuit and the length of the cable run from the transformer. This is often called the downstream short circuit current. This will determine the maximum kA rating required for the main circuit breaker.
For example, a typical 500kVA transformer has a short circuit current of 35kA at its terminals. The cable run from the transformer to the main breaker is 10m and is run with 90mm2 cable. The resistance in the cable limits how much current comes from the transformer, and so after calculations it was determined that the short circuit current at the end of the cable would be 26kA. In this case, a 20kA circuit breaker cannot be used in the installation.
It is outside the scope of this document to show how to calculate the short circuit current, but tables for this can be found on the internet. Another source is page 9-20 of the NHP Circuit Breaker Products catalogue.
Fortunately, not every circuit breaker in the installation needs to be rated above 26kA. Cascading is what happens when you place a smaller kA rated circuit breaker on the load side of a larger kA rated circuit breaker (for example, a 6kA circuit breaker downstream from a 20kA circuit breaker). In these cases, the larger circuit breaker limits a certain amount of the fault current, thus enabling you to safely use smaller rated circuit breakers downstream.
You can determine what size circuit breakers can be cascaded from the manufacturers. These are usually listed as cascade tables. You need to consult these tables, because you can't just use any smaller breaker size downstream. For example, the cascade tables may show that you can use a 6kA breaker downstream from a 20kA breaker. However, you probably can't use a 3kA breaker - the 20kA breaker just doesn't provide enough protection.
The most common mistake on large installations is that the kA rating of the circuit breaker was not taken into account when designing the circuit. Instead, the cheapest circuit breaker is chosen that meets the required standard current draw. The author has seen this himself a number of times (in fact, the example used above in the document did actually occur - a 20kA circuit breaker was used on the site when it needed a minimum rating of 26kA).
It is becoming more and more common for larger transformers to be used to power domestic installations. This has created a situation where the short circuit currents are much higher than they used to be. A typical transformer to power a street of houses may have been 100kVA. Now it is not uncommon to see 300kVA or even 500kVA transformers. This can result in short circuit currents of 20kA and above. To make matters worse, a number of well known manufacturers sell cheap low quality circuit breakers that have a rating of only 3kA. Electricians are continuing to use these to wire these without understanding the full ramifications of their decision.
The kA rating of a circuit breaker is a very important safety aspect to consider when designing a circuit. Without it, there is a good chance that a serious accident will occur. It only takes a few minutes to do the calculations when you have the correct tables.
The author has personally seen an incident where an incorrect kA rating caused a man to receive burns to 60% of his body. It could happen to you. Be safe and always consider the kA ratings in your design.
3) Application type
There are 3 MCB types, Type B, Type C and Type D, and the speed at which they trip depends upon the level of overload, and is usually determined by a thermal device within the MCB.
All 3 MCB types use a magnetic fault protection, which trips the MCB within one tenth of a second when the overload reaches a set level.
- Type B trips between 3 and 5 time full load current;
- Type C trips between 5 and 10 times full load current; and
- Type D trips between 10 and 20 times full load current.